EQP LOGIC EDITOR
Version 6.0
Item 25 - Beeper Volume
The volume level of the internal beeper can be adjusted with this variable. Values from 1 (lowest) to 4 (highest)
are allowed.
Beeper Volume
Value Description
1
Off
2
Low
3
Medium
4 High
Item 26 - Channel Type
This variable is used to configure device channels. See Section EQ37EDIO-SIL for more details.
Value Denition
1
Input
2
Output
3
Smoke Detector
4 Class A Output A (First of the pair)
5 Class A Output B (Second of the pair)
6 Class A Input A (First of the pair)
7 Class A Input B (Second of the pair)
8 Solenoid Output
9 Class A Solenoid Output A (First of the pair)
10 Class A Solenoid Output B (Second of the pair)
11 Class A Smoke Input A (First of the pair)
12 Class A Smoke Input B (Second of the pair)
Item 27 - Low Alarm Latching
When this configuration variable is set low alarms are latched until the unit is power cycled or a reset command
is issued.
Item 28 - High Alarm Latching
When this configuration variable is set high alarms are latched until the unit is power cycled or a reset command
is issued.
Item 29 - DCU Type Code
See the DCU section for a description of this variable.
DEVICE ITEM NUMBER DESCRIPTIONS